Advanced
A 22 kV utility transformer feeds a 480Y/277 V, 3-phase secondary at 1500 kVA. The transformer impedance is 5.75 percent. Approximate available fault current at the secondary terminals (assuming infinite primary) is:
1,800 A
Approximately 31,000 A (full-load amperes / impedance).
10,500 A
5,000 A